NESC C2-1997(section14)


 

  Storage batteries shall be located within a protective enclosure or area accessible only to qualified persons. A protective enclosure can be a battery room, control building, or a case, cage or fence that will protect the contained equipment and limit the likelihood of inadvertent contact with energized parts. Proper eye protection and clothing shall be provided in the battery area during battery maintenance and installation and shall consist of the following: goggles or face shield, acid-resistant gloves, protective aprons and overshoes, portable or stationary water facilities or neutralizing agent for rinsing eyes and skin. Safety signs inside and outside of a battery room or in the vicinity of a battery area, prohibiting smoking, sparks, or flame shall be provided.